Product Details
The kit includes parameters for measuring pressure with a low pressure range of (10") to 100 PSIG, and a differential range of 10-40 PSIG, while the high pressure range is set between 150-450 PSIG with a fixed differential of 70 PSI drop. It provides options for automatic or manual reset for high pressure settings. The equipment features cap connections that extend 48 inches with a flare nut, supporting full load amps at 120/240VAC, rated at 24A, as well as locked rotor amps at 120/240VAC, rated at 144A. Additionally, it accommodates pilot duty volt amps at 120/240VAC, equating to 720VA.