Product Details
The automatic reset high, low, and condenser fan cycling pressure switches are designed with a low pressure that opens at 5 PSI and closes at 20 PSI, with a tolerance of +/- 15 PSI. They feature a high pressure SPST that opens on pressure rise, a low pressure SPST that opens on pressure fall, and a condenser fan cycling SPST that also opens on pressure fall. The switches come with a 1/4" female SAE connection and utilize a snap acting stainless steel hermetically sealed sensor (SHP, SLP & SFC). Their small size and lightweight design allow for direct mounting, ensuring excellent set point repeatability and stability. The pressure range is from 0 to 650 PSI, with a burst pressure of 5000 PSI. They are rated for a life of 100,000 cycles at rated load, with a voltage rating of 50/60 Hz, compatible with 24/120/240 V (6 RLA, 36 LRA). The ambient temperature range is from 20°F to 176°F (-30°C to 80°C), while the fluid temperature range spans from 60°F to 250°F (-50°C to 120°C).