Product Details
The Honeywell flame amplifier R7886A1001 is designed for use with 7800 series and R7140 relay modules, offering a flame failure response time of either 0.8 or 3.0 seconds. The amplifier provides a flame signal strength range from 0.0 to 5.0 VDC and connects to the 7800 relay module through a printed circuit board edge connector that is keyed for proper orientation. It includes flame signal test jacks for measuring amplifier flame signal voltage, while color-coded labels identify the flame detection type. The dynamic self-check amplifier continuously tests the detectors and all electronic components in the flame detection system, and the 7800 series relay module locks out on safety shutdown in the event of flame detection system failure. This amplifier is compatible with existing Honeywell flame detectors, which are sold separately.