Product Details
The kit includes an ambient compensated temperature range of -20° to +60° C and features differential single phasing protection specifically designed for three-phase operation. It is equipped with adjustable bi-metallic elements that require no heaters, and it has been precisely factory calibrated and tested. The device comes with 1NO and 1NC electrically isolated alarm contacts, which can be set for either manual or automatic reset, a feature that is field changeable. For three-phase applications, a 3 pole overload relay is included, while a 2 pole overload relay is provided for one-phase applications, ensuring compliance with UL class 10 operation. High inertia start overloads are available upon consultation with the factory. Additionally, the kit features a large and easy-to-operate "Reset" button, a "Stop" button of similar design, and a "Trip" indicator that shows the status of the overload.