Product Details
The Honeywell flame amplifier R7861A1034 is designed for use with 7800 series and R7140 relay modules, offering a flame failure response time option of 0.8 or 3.0 seconds. The flame signal strength ranges from 0.0 to 5.0 VDC, and it plugs into the 7800 relay module via a printed circuit board edge connector keyed for proper orientation. The amplifier includes flame signal test jacks to measure flame signal voltage and features color-coded labels to identify the flame detection type. It incorporates a dynamic self-check function that tests the detectors and all electronic components within the flame detection system. The 7800 series relay module provides lockout on safety shutdown in case of flame detection system failure. This amplifier is compatible with existing Honeywell flame detectors, which are ordered separately.