Product Details
The CycleGard® CG400 Series CGT450-2060 low water cut-off is an automatic reset device designed for direct boiler mounting that eliminates the need for blowdowns. It features an intermittent level test for maximum protection of foaming boilers, with a burner circuit that opens after a 15-second delay during low water conditions to prevent short cycling from momentary water level fluctuations. The burner circuit automatically reactivates 30 seconds after water reaches the probe, allowing the optional water feeder to raise the water level above the probe. This model performs the intermittent level test every 20 minutes for 60 seconds. It includes a low water indicating light and implements a 15-second burner off delay and a 30-second burner on delay. The unit operates at 120V and is made in the USA.