Welcome to BuySupply.comNet terms available for approved accounts
BUSB974583GEC | Mfr. Model CG450-2060

CG400 Series CG450-2060 Low Water Cut-Off, Auto Reset, Direct Boiler Mounting, 120V

Cyclegard® CG400 Series CG450-2060 Low Water Cut-Off, Auto Reset, Direct Boiler Mounting, 120V

Contract eligible | Brand: Hydrolevel
Available to orderShips from stockSold per EA
Business price$335.41

Sign in for customer-specific pricing, tax exemption, saved lists, and invoice terms.

Request Bulk Quote

Product Details

The CycleGard® CG400 series CG450-2060 low water cut-off is an auto-reset device designed for direct boiler mounting and operates on 120V. It features an intermittent level test (ILT) that performs maximum boiler protection by removing power from the burner circuit at set intervals, with the CG450-2060 model performing the ILT every 20 minutes for 60 seconds. The unit includes a 15-second burner off delay and a 30-second burner on delay to prevent short cycling caused by momentary water level fluctuations, and the burner circuit contacts open after the 15-second delay when a low water condition is detected. It automatically reactivates the burner circuit 30 seconds after water reaches the probe, allowing an optional water feeder to raise the water level above the probe. Additional features include a low water indicating light and direct boiler mounting which eliminates the need for blowdowns. The product is made in the USA.

Specifications

BuySupply SKU
BUSB974583GEC
Manufacturer Part Number
CG450-2060
UPC
064227760206
UNSPSC
40101700
Brand
Hydrolevel
Manufacturer
Hydrolevel
Unit of Measure
EA
Minimum Order
1
Order Increments
1
Category
HVAC & Fans > HVAC Accesories & Parts > Hydronic Hardware & Parts
Shipping Weight
4 lb
Shipping Dimensions
7 W x 5.5 D x 9.5 H in

Business Purchasing

Account checkout required Tax exempt support Multi-user approvals Reorder list compatible

Sourcing support

Need help matching a part?

Send a manufacturer part number or request help finding an equivalent item for your approved account.

Email Sourcing Call 646.213.2345

Monday – Thursday, 9:30 AM – 5:30 PM ET

Friday, 9:30 AM – 4:30 PM ET

Alternatives

Replacement and similar products