Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, ensuring to confirm whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor. Next, select the control power used to close the contactor and then choose the overload by selecting a current range that contains the FLA of the motor. The options for the starter can be narrowed down based on incoming power configurations, including direct-online starters or separate control voltage setups. Additionally, configurations can include remote start terminals, assuming the line voltage and control voltage are the same or introducing separate control voltages if different. Key features of the starter include 9A, three-phase capability, separate control voltage, a reset button only, a 24-60V AC/DC coil, a 7.6-10A overload relay, and a NEMA 4X polycarbonate enclosure.