Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters designed for motors up to 60HP or 80A. These assembled motor starters consist of a contactor, an overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, verify the full load amperage (FLA) on the motor or equipment nameplate based on the supplied input voltage, and confirm whether the power is single-phase or three-phase. Choose a starter rated for current (amps) higher than the FLA of the motor. The control power used to close the contactor, the overload current range that contains the motor's FLA, and the preferred incoming power configuration must also be determined. Options include a direct-on-line starter, separate control voltage, remote start terminals, or a combination of these features if different voltages for line and control power are necessary. Key features include a 9A three-phase separate coil voltage with a reset button, a coil voltage range of 250-500V AC/DC, and an overload relay range of 7.6-10A, all housed within a NEMA 4X polycarbonate enclosure.