Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) on the motor or equipment nameplate at the input voltage, ensuring to confirm if it is 1-phase or 3-phase power. Choose a starter rated for current higher than the FLA of the motor. The control power used to close the contactor should be selected, along with the overload by choosing a current range that includes the FLA. Optional criteria for selection include incoming power configurations: a direct-online starter if line power serves as the control power, separate control voltage if the control voltage differs from the line voltage, or remote start terminals for activation from an external switch. The features include a 9A 1-phase separate coil voltage start/stop with a 100-250V AC/DC coil, a 5.7-7.6A overload, and the NEMA 4X polycarbonate enclosure.