Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, and confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current higher than the FLA of the motor, select the control power to close the contactor, and choose the overload by selecting a current range that contains the FLA of the motor. The options for selection include incoming power configurations: "direct-online starter" if the line power is also used as control power, "separate control voltage" if the control voltage differs from the line voltage, or "remote start terminals" for activation from an external switch. The features include a 16A 3-phase separate coil voltage with remote start terminals, start/stop capability, a 100-250V AC/DC coil, and a 10-13A overload relay in a NEMA 4X polycarbonate enclosure.