Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A, which include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) at the input voltage on the motor or equipment nameplate, ensuring to confirm whether the motor operates on 1 phase or 3 phase power. Choose a starter rated for a current (amps) higher than the FLA of your motor, select the control power for the contactor, and choose the overload by selecting a current range that encompasses the FLA. Options to further narrow down selections include whether the incoming power will be used as control power ("direct-online starter"), if separate control voltage is needed, and whether remote start terminals are required for external switch activation. Key features include a 16A 1 phase separate control voltage reset button, a 24-60V AC/DC coil, and a 13-16A overload relay within a NEMA 4X polycarbonate enclosure.