Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters designed to handle motors up to 60HP or 80A. Each assembled motor starter includes a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage, confirming whether it is 1-phase or 3-phase power. Choose a starter that has a current rating higher than the FLA of your motor, select the control power for the contactor, and choose the overload by selecting a current range that encompasses the FLA. Optional criteria for selection include incoming power types: "direct-online starter" if line power is the control power, "separate control voltage" if different, or "remote start terminals" if activated from an external switch. Key specifications include 26A 3-phase with separate coil voltage for start/stop operations, a coil voltage range of 250-500V AC/DC, and an overload relay rated for 13-16A. The product complies with relevant standards and is designed for effective motor management in various industrial applications.