Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, ensuring to confirm whether it is single-phase or three-phase power. Choose a starter rated for current higher than the FLA of your motor and determine the control power to close the contactor. The overload should be selected based on a current range that contains the FLA. Optional criteria for selection include incoming power options: "direct-online starter" for the same line and control voltage, "separate control voltage" for different voltages, and "remote start terminals" if activation from an external switch is needed. Features include 26A 1 phase separate coil voltage start/stop and a 100-250V AC/DC coil, with an overload protection of 20-24A. The enclosure is NEMA 4X polycarbonate rated, ensuring durability and compliance with industry standards.