Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A, which include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, it is essential to verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, ensuring that the starter is rated for a current higher than the FLA and confirming if it is single-phase or three-phase. The control power used to close the contactor must also be chosen, followed by selecting the overload from a current range that includes the FLA. Options for selection include whether the incoming power will also serve as control power, categorizing the starter as either a "direct-online starter" or requiring "separate control voltage," and the preference for "remote start terminals" if activation from an external switch is needed. The specific features of the kit include 38A, 3 phase, separate control voltage, start/stop capability, a 24-60V AC/DC coil, 29-35A overload, and the NEMA 4X polycarbonate enclosure for durability.