Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, ensuring to confirm whether it is 1-phase or 3-phase power to the motor. Choose a starter rated for current (amps) higher than the FLA of your motor and select the control power used to close the contactor. The overload should be chosen by selecting a current range that contains the FLA of the motor. The optional criteria for selection include the incoming power type: a "direct-online starter" if the line power is used as control power, "separate control voltage" if the control voltage differs from the line voltage, and "remote start terminals" if the starter needs to be activated from an external switch. The features of the motor starter include 52A 3-phase direct online start/stop, a 100-250V AC/DC coil, and an overload relay rated for 44-53A, housed in a NEMA 4X polycarbonate enclosure.