Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A, which include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, ensuring to confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current (amps) higher than the FLA. The control power used to close the contactor must also be determined, alongside selecting an overload with a current range containing the FLA. The options available include a direct-online starter when line power is also used as control power, separate control voltage if different, and remote start terminals for activation from an external switch, with configurations available for when line and control voltages differ. The features of the product include a 52A 1-phase direct online start/stop capability, a 100-250V AC/DC coil, and a 36-47A overload protection, all housed in a durable NEMA 4X polycarbonate enclosure.