Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage to be supplied, confirming whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor, and select the control power used to close the contactor. Choose the overload by selecting a current range that contains the FLA of the motor. Optional criteria for selecting your starter include incoming power configuration: "direct-online starter" for line power used as control power, "separate control voltage" if the control voltage differs from line voltage, and "remote start terminals" for activation from an external switch, assuming line and control voltages are the same. For setups requiring both different voltages and remote start terminals, select "separate control voltage + remote start terminals." Key features include a 65A three-phase separate coil voltage with remote start terminals for start/stop control, a 100-250V AC/DC coil, and a 57-67A overload relay, all housed in a NEMA 4X polycarbonate enclosure.