Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters suitable for applications up to 60HP or 80A. The assembled motor starters include a contactor, an overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, begin by verifying the full load amperage (FLA) of the motor at the input voltage specified on the equipment nameplate, confirming whether the power supply is single-phase or three-phase. Choose a starter rated for current higher than the motor's FLA, then select the control power for closing the contactor and the overload relay based on a current range that encompasses the FLA identified. Additional selection criteria include choosing between a direct-online starter, separate control voltage, or remote start terminals if external activation is needed. The key features of the starter include a 65A rating, suitable for single-phase applications, direct online operation, a reset button, a coil voltage range of 100-250V AC/DC, and an overload relay rated between 57-67A, all encapsulated in a NEMA 4X polycarbonate enclosure.