Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60 HP or 80 A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage, confirming whether it is single-phase or three-phase power. Choose a starter rated for current higher than the FLA of the motor and select the control power used to close the contactor. Additionally, select the overload based on a current range that contains the motor's FLA. Optional criteria for selection include incoming power configurations such as "Direct-On-Line Starter" for the same line and control power, "Separate Control Voltage" for different voltages, or "Remote Start Terminals" for activation from an external switch. The motor starter features include 80 A capacity, three-phase operation, separate coil voltage, start/stop functionality, a 250-500 V AC/DC coil, 48-60 A overload relay, and a NEMA 4X polycarbonate enclosure.