Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage, confirming whether it is 1-phase or 3-phase power. Choose a starter rated for a current (amps) higher than the FLA of your motor, along with the control power used to close the contactor, and select the overload by choosing a current range that contains the FLA of the motor. Additionally, the selection criteria include incoming power options, whether using a direct-online starter, separate control voltage, or remote start terminals. Key features include a 65A rating with 1-phase separate control voltage, a reset button, a coil voltage of 24-60V AC/DC, and a 50-60A overload relay, all housed in a NEMA 4X polycarbonate enclosure.