Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A, which consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage and confirm if it is single-phase or three-phase power. It is essential to choose a starter rated for current (amps) higher than the FLA of your motor. Additionally, select the control power used to close the contactor and choose the overload by selecting a current range that includes the FLA from the motor. The options available for selection include incoming power configurations such as "direct-online starter," "separate control voltage," or "remote start terminals," with the possibility of combining separate control voltage and remote start terminals if different voltages are used for line and control power. This specific model features a current rating of 80A, is single-phase, incorporates separate control voltage with remote start terminals, and operates with a start/stop functionality using a 24-60V AC/DC coil and a 75-87A overload relay, all housed within a NEMA 4X polycarbonate enclosure.