Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) on the motor or equipment nameplate at the input voltage you will supply, confirming whether it is 1-phase or 3-phase power. Select a starter rated for current (amps) higher than the FLA of your motor. Choose the control power used to close the contactor and select the overload by choosing a current range that includes the FLA of the motor. Additional criteria include selecting the incoming power: for a direct-online starter, the line power is used as control power, while a separate control voltage indicates different line and control voltages. Remote start terminals can be added for activation from an external switch. Key features of this starter include a 9A 3-phase separate coil voltage start/stop, 100-250V AC/DC coil, and 2.3-3.1A overload protection, all housed in a NEMA 4X polycarbonate enclosure.