Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60 HP or 80 A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, confirm the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, ensuring the distinction between single-phase and three-phase power. Choose a starter rated for current (amps) higher than the FLA. The control power used to close the contactor should be determined, and the overload must be selected based on a current range containing the FLA. Optional criteria for selection include incoming power type, such as "direct-online starter" for same line and control power, or "separate control voltage" for differing voltages. If external activation is needed, terminals can be added for "remote start terminals." For the specified configuration, features include 38 A rating, three-phase compatibility, direct online operation, start/stop functionality, a 100-250V AC/DC coil, 35-40 A overload capacity, and a durable NEMA 4X polycarbonate enclosure.