Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, first verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, ensuring to confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor and select the control power used to close the contactor. Next, choose the overload by selecting a current range that contains the FLA of the motor. The product options include a starter with 9A 3-phase separate control voltage and remote start terminals, a start/stop 24-60V AC/DC coil, and a 7.6-10A overload. The product is designed to meet NEMA 4X standards, ensuring protection from dust and water ingress.