Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, first refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, confirming whether it is 1-phase or 3-phase power to the motor, and ensure the starter is rated for current (amps) higher than the FLA of your motor. Next, choose the control power used to close the contactor and select the overload by identifying a current range that contains the FLA of the motor. Additionally, criteria for selection include incoming power options: a "direct-online starter" if line power is also used as control power, "separate control voltage" if the control voltage differs from line voltage, and options for "remote start terminals" if activation occurs from an external switch with the same line and control voltage. If different voltages are used, the configuration would be "separate control voltage + remote start terminals." This specific model features a 9A 3-phase separate coil voltage with remote start terminals, a start/stop range of 100-250V AC/DC coil, a 5.7-7.6A overload, and is housed in a NEMA 4X polycarbonate enclosure.