Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters designed for applications up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, users should verify the full load amperage (FLA) from the motor or equipment nameplate, ensuring to account for whether the power supply is 1-phase or 3-phase. It is essential to choose a starter rated for current (amps) that exceeds the FLA. Additionally, users must select the control power needed to activate the contactor and choose an overload relay that includes the FLA within its current range. Optional criteria for selection include incoming power options: a direct-online starter uses the line power as control power, whereas a separate control voltage indicates a different control voltage. Remote start terminals can be included to accept external control inputs, which can be configured for separate control voltage situations. Notable features of the product include a 9A 3-phase separate coil voltage with remote start terminals, a reset button, and a coil rating of 250-500V AC/DC, along with overload relays rated at 1.7-2.3A.