Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, and confirm whether it is single-phase or three-phase power. Choose a starter rated for a current (amps) higher than the FLA of your motor. The control power used to close the contactor must also be chosen, along with selecting an overload that contains the motor's FLA. Optional criteria for selection include incoming power types: direct-online starter, separate control voltage, or remote start terminals for activation from an external switch. The features of the motor starter include a 9A rating, single-phase configuration, remote start terminals, a reset button, a control coil voltage range of 100-250V AC/DC, and an overload range of 7.6-10A, all housed within a NEMA 4X polycarbonate enclosure.