Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage. Confirm whether it is 1-phase or 3-phase power to the motor and choose a starter rated for current (amps) higher than the FLA of your motor. Select the control power used to close the contactor and choose the overload by selecting a current range that contains the FLA of the motor. The optional criteria for selecting a starter include incoming power options such as "direct-online starter," "separate control voltage," and "remote start terminals" for activation from an external switch. If using different voltages for line and control power, choose "separate control voltage + remote start terminals." Key features include a 12A, 3-phase configuration, remote start terminals, start/stop functionality, a 250-500V AC/DC coil, a 3.1-4.2A overload relay, and a NEMA 4X polycarbonate enclosure.