Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, refer to the motor or equipment nameplate to determine the full load amperage (FLA) at the input voltage, ensuring to confirm whether the motor operates on 1 phase or 3 phase power. Choose a starter rated for current (amps) higher than the FLA of the motor. Select the control power used to close the contactor and choose the overload by selecting a current range that includes the FLA determined earlier. The options for the starter selection include incoming power configurations such as direct-online starter if the line power is also used for control, separate control voltage if the control voltage differs from the line voltage, and remote start terminals for external switch activation. Key features encompass 12A 3 phase capabilities, remote start terminals for start/stop functionality, a 100-250V AC/DC coil, and an overload range of 2.3-3.1A, all housed in a NEMA 4X polycarbonate enclosure.