Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters suitable for motors up to 60HP or 80A. The assembled motor starters consist of a contactor, an overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, reference the motor or equipment nameplate to verify the full load amperage (FLA) at the supplied input voltage, ensuring to identify whether the motor operates on 1-phase or 3-phase power. The starter should be rated for current (amps) higher than the FLA. Next, choose the control power for closing the contactor and select the overload based on a current range that includes the motor’s FLA. The options include a "Direct-Online Starter" for line power used as control power, "Separate Control Voltage" when the control voltage differs from line voltage, and configurations for "Remote Start Terminals" if external activation is required. Key features of the motor starter include ratings of 12A and 3-phase operation, a separate coil voltage, start/stop functionality, and a 100-250V AC/DC coil alongside a 10-13A overload relay. The dimensions and specifications are designed to meet NEMA 4X standards for enhanced durability in various environments.