Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. The specifications include a current rating of 12A for 3-phase applications with a separate coil voltage, a reset button only feature, and a coil voltage range of 250-500V AC/DC. Additionally, the overload relay is rated for 10-13A. To select the proper starter for your requirements, verify the full load amperage (FLA) at the input voltage and confirm the phase type of the motor. Choose a starter rated for current higher than the FLA, select the control power used to close the contactor, and pick the appropriate overload range. Incoming power options include direct-online starters, separate control voltage, and configurations for remote start terminals, accommodating variations in line and control voltage as needed.