Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, it is essential to refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage, confirming whether it is single-phase or three-phase power. A starter rated for current (amps) higher than the FLA should be chosen, along with the appropriate control power for the contactor. The overload should be selected from a current range that includes the FLA. Optional criteria for selection include incoming power arrangements; options are available for direct-online starters, separate control voltage configurations, or remote start terminals for external switch activation. The specific features of this unit include a 16A rating, 3-phase operation, a separate coil voltage with remote start terminals, a reset button only, a 100-250V AC/DC coil, a 16-20A overload relay, and NEMA 4X polycarbonate construction.