Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60 HP or 80 A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, ensuring to confirm whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor, select the control power used to close the contactor, and choose the overload by selecting a current range that contains the FLA from step one. Once this is done, narrow down the starters to suitable options based on optional criteria such as incoming power: "direct-online starter" if the line power is used as the control power, "separate control voltage" if the control voltage differs from the line voltage, or "remote start terminals" for activation from an external switch. The features of this motor starter include a 16 A three-phase separate coil voltage reset button, a 100-250 V AC/DC coil, and a 7.6-10 A overload relay, all housed in a NEMA 4X polycarbonate enclosure.