Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters suitable for applications up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage, ensuring to confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current higher than the FLA. The control power used to close the contactor, as well as the overload by selecting a suitable current range, must also be considered. Optional criteria include incoming power configurations, such as "direct-online starter" if line power is also used as control power, or "separate control voltage" if different. For starters needing activation from an external switch, terminals for remote control power input can be added, indicated as "remote start terminals." The specific model features a 26A 3-phase separate coil voltage, remote start terminals, start/stop capabilities, a 100-250V AC/DC coil, and a 10-13A overload relay, all housed in a NEMA 4X polycarbonate enclosure.