Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) from the motor or equipment nameplate at the input voltage, ensuring to check for 1-phase or 3-phase power. Choose a starter rated for current (amps) higher than the FLA, select the control power for the contactor, and choose the overload by selecting a current range that encompasses the FLA. Options for incoming power include "direct-online starter" if line power is also used for control power, or "separate control voltage" if different. Additionally, for activation from an external switch, remote start terminals can be added, with considerations for voltage compatibility. Key features include a 26A 1-phase separate control voltage start/stop with a coil rated for 24-60V AC/DC and a 24-29A overload relay, all housed in a NEMA 4X polycarbonate enclosure.