Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, confirming whether it is 1-phase or 3-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor and select the control power used to close the contactor. The overload should be chosen based on a current range that contains the FLA from the previous step. Optional criteria for selection include incoming power configurations: "direct-online starter" if line power is used as control power, "separate control voltage" if the control voltage differs from line voltage, and options for "remote start terminals" if the starter needs to be activated from an external switch. Features include 26A 3-phase remote start terminals, a reset button, a coil voltage range of 100-250V AC/DC, and a 24-29A overload relay, all within a NEMA 4X polycarbonate enclosure.