Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60 HP or 80 A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter for your requirements, verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, confirming whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor, and select the control power for closing the contactor. The overload should be chosen from a current range that includes the FLA. Optional criteria for selection include incoming power configuration: a direct-online starter if line power is used as control power, a separate control voltage if the control voltage differs, or a setup with remote start terminals for activation from an external switch. The specific features of this kit include a rating of 38 A, compatibility with three-phase power, separate control voltage, a reset button, a 24-60V AC/DC coil, and an overload relay rated for 24-29 A, all housed within a NEMA 4X polycarbonate enclosure.