Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, it is essential to refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage supplied, confirming whether the system is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of the motor, select the control power used to close the contactor, and choose the overload by selecting a current range that encompasses the FLA. The selection process may also involve optional criteria including incoming power configurations such as "direct-online starter" for matching line and control voltages, "separate control voltage" for different voltages, or "remote start terminals" for activation via an external switch. The features of this specific model include a 38A rating, operation with 1 phase power, separate control voltage, a reset button only, a 24-60V AC/DC coil, a 20-24A overload relay, and NEMA 4X polycarbonate construction.