Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage supplied, ensuring to check if it is 1-phase or 3-phase power. Choose a starter rated for current (amps) higher than the FLA of the motor. Select the control power used to close the contactor and choose the overload by selecting a current range that contains the FLA of the motor. Optional criteria include incoming power: if line power will be used as the control power, this is a "direct-online starter," while if the control voltage differs from the line voltage, it is "separate control voltage." For activation from an external switch, terminals can be added for "remote start terminals," assuming line and control voltage are the same. If remote start terminals are needed with different voltages for line and control power, it is referred to as "separate control voltage + remote start terminals." The features of the system include a 38A 1-phase separate coil voltage start/stop with a 100-250V AC/DC coil and 16-20A overload, housed in a NEMA 4X polycarbonate enclosure.