Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, first refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, confirming whether it is single-phase or three-phase power to the motor, and choosing a starter rated for current (amps) higher than the FLA of your motor. Next, select the control power used to close the contactor and choose the overload by selecting a current range that contains the FLA of the motor. Optional criteria for selecting your starter include incoming power configurations such as "Direct-On-Line Starter" when line power is used as control power, or "Separate Control Voltage" when line and control voltages differ. If activation from an external switch is needed, remote start terminals can be added, which assume that line and control voltages are the same; otherwise, "Separate Control Voltage + Remote Start Terminals" is applicable for different voltages. Key features include a 38A 3-phase separate coil voltage, remote start terminals, a reset button, coil voltage options of 250-500V AC/DC, and a 20-24A overload capacity, all contained within a durable NEMA 4X polycarbonate enclosure.