Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage and confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current higher than the FLA of your motor and select the control power used to close the contactor. Choose the overload by selecting a current range that contains the FLA of the motor. Optional criteria include the incoming power, with options for direct-online starter, separate control voltage, or configurations with remote start terminals. The features include a 52A three-phase separate coil voltage start/stop with a 250-500V AC/DC coil, 25-33A overload protection, and a NEMA 4X polycarbonate enclosure.