Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, verify the full load amperage (FLA) at the input voltage on the motor or equipment nameplate, ensuring you confirm whether it is 1-phase or 3-phase power. Choose a starter rated for current higher than the FLA of your motor, select the control power used to close the contactor, and then choose the overload by selecting a current range that contains the FLA of the motor. When narrowing down the options, consider the incoming power type; if the line power will be used as the control power, select a "direct-online starter." If the control voltage differs from the line voltage, it is considered "separate control voltage," and if activation from an external switch is needed, add terminals for "remote start terminals." The product specifications include features such as 52A 1 phase remote start terminals, a reset button, a 100-250V AC/DC coil, and a 25-33A overload relay, all housed in a NEMA 4X polycarbonate enclosure.