Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters include a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter, verify the full load amperage (FLA) at the input voltage from the motor or equipment nameplate, confirming whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor and select the control power for the contactor. The overload should be chosen from a current range that contains the FLA identified earlier. Options include: direct-online starter if the line power is used as the control power, separate control voltage if the control voltage differs from the line voltage, and remote start terminals for activation from an external switch, which assumes that line and control voltages are the same. For different voltages, "separate control voltage + remote start terminals" is available. The key features include a 65A rating, three-phase operation, separate control voltage, a reset button, a coil voltage of 24-60V AC/DC, a 50-60A overload relay, and a NEMA 4X polycarbonate enclosure.