Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters designed for motors up to 60HP or 80A. The assembled motor starters include a contactor, an overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, start by verifying the full load amperage (FLA) from the motor or equipment nameplate considering the input voltage, and ensure the correct power phase (single-phase or three-phase). Choose a starter with a current rating that exceeds the FLA. Next, select the control power for closing the contactor and choose an overload current range that encompasses the motor's FLA. Additional selection criteria include the type of incoming power; options include a "direct-online starter," "separate control voltage," and configurations with "remote start terminals." Key features of the starters include a rating of 65A, suitable for three-phase operation, a direct online configuration, a reset button, a coil operating range of 100-250V AC/DC, and an overload range of 57-67A, all housed in a NEMA 4X polycarbonate enclosure.