Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A, which consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, verify the full load amperage (FLA) from the motor or equipment nameplate and confirm if it is 1-phase or 3-phase power. Choose a starter with a current rating higher than the FLA, select the control power used to close the contactor, and then choose the overload by selecting a current range that encompasses the FLA. Optional criteria include incoming power configuration: "direct-online starter" if line power is used as control power, "separate control voltage" for different line and control voltages, or incorporating "remote start terminals" for activation from an external switch. The specific model features include 65A 1-phase capability, remote start terminals, a reset button, a 100-250V AC/DC coil, and an overload range of 57-67A, all housed within a NEMA 4X polycarbonate enclosure.