Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. Assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, first refer to the motor or equipment nameplate to verify the full load amperage (FLA) at the input voltage you will supply, ensuring you confirm whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor. Next, select the control power used to close the contactor, and choose the overload by selecting a current range that encompasses the FLA of the motor. After determining these factors, select your starter based on optional criteria concerning incoming power. The options include a direct-online starter if line power is used as the control power, separate control voltage if the control voltage differs from the line voltage, and remote start terminals for activation from an external switch. Key features include 80A, 3 phase capability, separate control voltage, start/stop functionality, a 24-60V AC/DC coil, a 65-78A overload relay, and the NEMA 4X polycarbonate enclosure.