Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the proper starter for your requirements, first verify the full load amperage (FLA) at the input voltage supplied, confirming whether it is single-phase or three-phase power. Choose a starter rated for current (amps) higher than the FLA of your motor. Next, select the control power used to close the contactor, followed by selecting the overload by choosing a current range that includes the FLA from your motor. Optional criteria for selection include incoming power options, such as direct-online starter if line power is used as the control power, or separate control voltage if they differ. If the starter must be activated from an external switch, remote start terminals can be added. Key features of the motor starter include 80A rating, single-phase operation, separate coil voltage, remote start terminals, a reset button, a 100-250V AC/DC coil, and overload relay settings of 65-78A, all housed in a durable NEMA 4X polycarbonate enclosure.