Product Details
Springer Controls manufactures a complete line of IEC enclosed AC motor starters suitable for applications up to 60HP or 80A. The assembled motor starters consist of a contactor, overload relay, and a NEMA 4X rated polycarbonate enclosure. To select the appropriate starter, verify the full load amperage (FLA) from the motor or equipment nameplate and confirm if the motor operates on 1-phase or 3-phase power. Choose a starter rated higher than the FLA of the motor, and select the control power type used to close the contactor. The overload should be chosen based on the current range that includes the FLA determined earlier. The starter can further be customized based on criteria such as incoming power type, which includes options for direct-online starters, separate control voltage configurations, or setups with remote start terminals for activating the starter from an external switch. Key features of this model include an 80A capacity, 1-phase separate control voltage with start/stop functionality, a 24-60V AC/DC coil, and an overload relay rated for 75-87A. The units are designed for compliance with applicable industry standards, ensuring reliable performance in demanding environments.